Warning system for decreasing fuel with electronic fuel level sender
Remote control system
Standby Rating for a standby engine should be sized for a maximum of 70% average load factor and roughly 200 hours per year. Standby power ratings should never be applied except in true emergency outage situations. With standby rated generators there is no overload capability built into the units.
Prime Power is the maximum power accessible at the variable load for an unlimited number of hours per year in a variable load setting. It is not advisable that the variable load exceed 70% average of the prime power rating during any operational period. If the engine is running at 100% prime power, yearly hours should not exceed 500. Overload situations should be avoided however a 10% overload capability is available for a 1 hour period within a 12 hour cycle of operation.
Continuous Power is used in applications where suppliying power is at a constant %100 load for an unlimited number of hours each year. Continuous power rated units are most widely used in applications where the power grid is unreachable.
QUALITY STANDARDS
Our generators are manufactured in compliance with VDE 0530, BSE 4999 BS5000, IEC 34, EN12601; EN60204-1; TS ISO 8528-1 … -13; EN12100-1; EN12100-2; EN61000-6-4; EN61000-6-2; EN61000-4-11; EN61000-4-6; EN61000-4-5; EN61000-4-2; EN55011; EN55016-2-1; EN55016-2-3; EN61000-3-2; EN61000-3-3; EN55014-1; EN61000-6-2; EN61000-4-3; EN61000-4-4; EN61000-4-8; EN61000-4-11; TS EN ISO 3744; TS EN ISO 3746; TS EN 60034-1; TS EN 60034-22; TS EN ISO 3046; BS 5514; NEMA MG 21; IEC 60034, BS 4999/5000 and TS EN 60947-1..4 standards.
We have ISO 9001-2015, ISO 14001-2015, ISO 45001-2018 and ISO 1002-2006 management system certificates from Kiwa, an accredited independent quality organization.
Our generators up to 400 kw are manufactured in compliance with 2000/14/EC European noise emission directive and certified from Ente Certificazione Macchine.
We also have TS ISO 8528-4, TS ISO 8528-5, TS EN 13501-1+A1:2013 flame retardancy and TTS EN ISO 9227 certificates against anti-corrosion together with CE Declaration.
Engine Specifications
Baudouin series heavy duty diesel engine
4 CYCLE, WATER COOLING SYSTEM, TURBOCHARGED - AFTERCOOLER INDUCTION
ECU / Electronic governor system
12/24 volt self-starter and charger alternator
Changeable air, fuel and oil filter
Flexible fuel pipe
Oil discharge valve and extention pipe
Industrial type silencer, exhaust spiral or compensator
Maintenance free battery
Engine block water heater (in automatic models)
Diesel gen-set maintenance and operating instructions and electrical circuit diagram
MODEL
6M21G500/5
POWER
STAND BY kW
450
PRIME kW
409
SPEED (rpm)
1500
CYCLE
4
DISPLACEMENT (lt)
12,54
NUMBER OF CYLINDERS
6, in line
BORE AND STROKE
127 x 165
COMPRESSION RATIO
16 : 1
GOVERNOR TYPE
ECU / Electronic
INDUCTION
TURBOCHARGED - AFTERCOOLER
COMBUSTION SYSTEM
DIRECT
COOLING SYSTEM
WATER
FUEL CONSUMPTION (lt/h)
100% OF PRIME POWER
95,9
75% OF PRIME POWER
69,6
50% OF PRIME POWER
46,6
TOTAL LUBRICATION SYSTEM CAPACITY (lt)
34
TOTAL COOLANT CAPACITY (lt)
47
Alternator Specifications
Brushless, single bearing, flexible disc 4 poles alternator for harmonic failure
H type isolation class
IP 21-23 protection class
Self exciter
Electronic automatic voltage regulator
Stator 2/3 step for harmonic failure
The alternator windings are protected by insulating varnish against oil and acid
BRAND
Stamford
MODEL
S4L1D-G
FREQUENCY (HZ)
50
POWER (KVA)
500
DESIGN
4 pole, brushless
CONNECTION TYPE
Star
VOLTAGE (V)
400
phase
3
A.V.R.
AS440
VOLTAGE REGULATION (+/-)
± 1%
INSULATION SYSTEM
Class H
PROTECTION
IP23
RATED POWER FACTOR
0,8
WEIGHT COMP. ALTERNATOR (KG)
1190
Genset Controllers
Datakom D-700
ONE SOLUTION FOR ALL GENSET APPLICATIONS.
FEATURES
128x64 graphical LCD display
Diesel and gas genset support
Supports up to 48 gensets
Automatic learning/self adjust
Direct governor & AVR control
Voltage and phase matching
kW & kVAr load sharing
Multiple topologies
6xCT, true mains metering
True soft transferin both ways
Peak Lopping / peak shaving (mains or genset priority)
Mains de-coupling protection
R.O.C.O.F protection
Vector shift protection
Reversepower protection
Over/under freq. Protection
Over/under voltage protection
Smart load management
Smart genset sequencing
Run/stop priority support
Equal agingof gensets
Base load (power export)
Unmanaged distributed power export support
AVR & GOV droop support
Dead bus sensing
400Hz operation support
400 event logs, full snapshot
All parameters front panel editable
3 level configuration password
Downloadable languages
Waveform display of V & I
Harmonic analysis of V & I
Synchroscope & check synch
12 configurable digital inputs
Inputs expandable to 44
8 configurable digital outputs
Outputs expandable to 38
7 configurable analog inputs
Both CANBUS-J1939 & MPU
3 configurable service alarms
Multiple automatic exerciser
Weekly operation schedule
Dual mutual standby with equal aging of gensets
Manual “speed fine adjust” on selected ECUs
Automatic fuel pump control
Disable protections feature
Excess power protection
Overload IDMT protection
Load shedding, dummy load
Multiple load management
Current unbalance protection
Voltage unbalance protection
Fuel filling & fuel theft alarms
Battery back-up real time clock
Idle speed control
Battery charge run enabled
Combat mode support
Multiple nominal conditions
Tactor & MCB drive
4 quadrant genset power counters
Mains power counters
Fuel filling counter
Fuel consumption counter
Modem diagnostics display
Configurable through USB, RS-485 and GPRS
Free configuration program
Allows SMS controls
Ready for central monitoring
Mobile genset support
Automatic GSM geo-location
GPS connectivity (RS232)
Dynamic DNS support
Easy USB firmware upgrade
IP65 rating with standard gasket
MEASUREMENTS
Mains & genset PN/PP voltages
Mains & genset frequency
Mains & genset phase currents
Mains & genset neutral currents
Mains & genset, phase & total, kW, kVA, kVAr, pf
Engine speed
Battery voltage
COMMUNICATIONS
Ethernet (10/100Mb)
4-band GPRS modem (optional)
USB Device
RS-485 (2400-115200baud)
RS-232 (2400-115200baud)
MicroSD card slot
J1939-CANBUS
Geo-locating through GSM
GPS support (RS-232)
Embedded web server
Web monitoring& programming
Internet Central Monitoring
SMS message sending
E-mail sending
Free PC software: Rainbow Plus
Modbus RTU
SNMP (with TRAP messages)
SNTP
FUNCTIONALITIES
Multi genset synch & load share
Mains synchronization
Single genset parallel with mains
AMF unit
ATS unit
Remote start controller
Manual start controller
Engine controller
Remote display panel
Internal battery (optional)
Remote display panel
GENSET CONTROLLERS FOR SYNCHRONIZATION SYSTEMS OPTIONAL
Next generation synchronizing genset controller capable of every communication and functionality.
DEEPSEA 8610
DEEPSEA 8620
DEEPSEA 8660
ComAp InteliGen BaseBox
ComAp InteliGen 200
Datakom D700
DEEPSEA 8610
DEEPSEA 8620
DEEPSEA 8660
ComAp InteliGen BaseBox
ComAp InteliGen 200
Multi genset synch & load share
✔
✔
╳
╳
✔
✔
Mains synchronization
✔
╳
╳
✔
╳
╳
Single genset parallel with mains
✔
╳
✔
✔
✔
✔
ATS unit
✔
✔
✔
✔
✔
✔
Remote start controller
✔
✔
╳
╳
✔
✔
Manual start controller
✔
✔
╳
╳
✔
✔
Engine controller
✔
✔
✔
╳
✔
✔
Data logging
✔
✔
✔
✔
✔
✔
Remote display panel
✔
✔
✔
✔
✔
✔
Ethernet (10/100Mb)
✔
✔
✔
✔
✔
OPTIONAL
4-band GPRS modem
OPTIONAL
OPTIONAL
╳
OPTIONAL
OPTIONAL
OPTIONAL
USB Device
✔
✔
✔
✔
✔
✔
RS-485 (2400-115200baud)
✔
✔
✔
✔
✔
✔
RS-232 (2400-115200baud)
✔
✔
✔
✔
✔
OPTIONAL
MicroSD card slot
✔
╳
╳
╳
╳
╳
J1939-CANBUS
✔
✔
✔
OPTIONAL
✔
✔
Geo-locating through GSM
✔
╳
╳
OPTIONAL
OPTIONAL
OPTIONAL
Embedded web server
✔
✔
✔
✔
✔
✔
Web monitoring& programming
✔
✔
✔
✔
✔
✔
Internet Central Monitoring
✔
✔
✔
✔
✔
✔
SMS message sending
✔
✔
╳
✔
✔
✔
E-mail sending
✔
╳
╳
╳
✔
✔
Free PC software
✔
✔
✔
✔
✔
✔
Modbus RTU
✔
✔
✔
✔
✔
✔
SNMP
✔
✔
╳
╳
✔
✔
Configurable digital inputs
12
12
12
11
12
8
Configurable digital outputs
8
8
8
8
12
8
Configurable analog inputs
7
4
4
0
3
4
Canopy
Modular type sound-proof canopy
Canopy installation executed with screw and nut, without welding process